तारको अर्को छेउमा कति भोल्ट पुग्छ?Check voltage at the far end of a cable
तारमा कति voltage drop हुन्छ?How much voltage will your wire lose?
तारको material, size, एकतर्फी दूरी, current र phase राख्नुहोस्। यो resistance मा आधारित सुरुवाती हिसाब हो, सुरक्षित wire size को अन्तिम निर्णय होइन।Enter the wire material, cross-sectional area, one-way length, current, and phase. This is a resistance-based first estimate, not a final cable selection.
भोल्टेज ड्रपको अनुमानVoltage-drop estimate
Within the entered 3% planning limit.
Cable को ampacity, breaker, fault current, earthing, insulation, grouping, conduit वा जमिनभित्रको installation, connection quality र local rule छुट्टै जाँच्नुपर्छ। Aluminium मा सही terminal र installation practice झन् जरुरी हुन्छ। योग्य electrician वा electrical engineer बाट design जाँच गराउनुहोस्।Cable ampacity, breaker protection, fault current, earthing, insulation, grouping, conduit or buried installation, termination quality, and local rules need separate checks. Aluminium also needs suitable terminals and installation practice. Have a qualified electrician or electrical engineer verify the design.
03
हिसाब कसरी हुन्छ?How the calculation works
लामो, तातो वा सानो तारको resistance बढी हुन्छ। Single-phase वा DC two-wire मा current जाने र फर्किने दुवै conductor गनिन्छ। Balanced three-phase मा √3 factor प्रयोग हुन्छ।A longer, hotter, or smaller conductor has more resistance. A single-phase or DC two-wire circuit includes both outgoing and return conductors. A balanced three-phase circuit uses the √3 factor.
ρT = ρ20 × [1 + α × (temperature − 20°C)]one-way resistance R = ρT × length ÷ areasingle-phase or DC drop = 2 × current × Rbalanced three-phase drop = √3 × current × Rdrop % = voltage drop ÷ nominal voltage × 100conductor loss = 2 × I²R (two-wire) or 3 × I²R (three-phase)
Copper का लागि ρ20 = 0.017241 Ω·mm²/m र α = 0.00393/°C। Conductor-grade aluminium का लागि ρ20 = 0.028264 Ω·mm²/m र α = 0.00403/°C। वास्तविक cable resistance फरक हुन सक्छ, त्यसैले उपलब्ध भए manufacturer को Ω/km data प्रयोग गरेर engineer ले फेरि जाँच्नुपर्छ।Copper uses ρ20 = 0.017241 Ω·mm²/m and α = 0.00393/°C. Conductor-grade aluminium uses ρ20 = 0.028264 Ω·mm²/m and α = 0.00403/°C. Real cable resistance can differ, so an engineer should recheck with the manufacturer's Ω/km data when available.
04
नमुना हिसाबWorked example
नमुनामा 230 V single-phase circuit, 4 mm² copper, 25 m एकतर्फी दूरी, 20 A load र 70°C conductor temperature राखिएको छ। Planning limit 3% हो।The example is a 230 V single-phase circuit using 4 mm² copper over a 25 m one-way run at 20 A and an estimated 70°C conductor temperature. The entered planning limit is 3%.
0.017241 × [1 + 0.00393 × 50] = 0.020629 Ω·mm²/m70°C मा resistivityresistivity at 70°C
0.020629 × 25 ÷ 4 = 0.1289 Ωएकतर्फी conductor resistanceone-way conductor resistance
2 × 20 × 0.1289 = 5.16 Vजाने र फर्किने conductor को dropdrop across outgoing and return conductors
5.16 ÷ 230 × 100 = 2.24%राखिएको 3% limit भित्रwithin the entered 3% limit
230 − 5.16 = 224.84 Vload मा अनुमानित voltageestimated voltage at the load
2 × 20² × 0.1289 = 103.1 Wदुवै conductor मा heat lossheat loss in both conductors
05
स्रोत र मान्यताSources and assumptions
- Nepal Department of Urban Development and Building Construction, NBC 207 Electrical Design Requirements, checked 4 Sep 2026. Nepal's public-building code requires conductor selection and electrical installation to follow the applicable wiring, rating, inspection, and safety requirements.
- Government of Nepal curriculum, Basic Electrical Installation and Workshop Technology, checked 4 Sep 2026. Its NBC 207 teaching material says conductor sizing must consider both current-carrying capacity and voltage drop, which is why this page does not turn the drop result into a safety approval.
- Minnesota Department of Labor and Industry, License Examination Guide, checked 4 Sep 2026. It derives approximate voltage drop from Ohm's law and uses factors 2 for single-phase and 1.732 for three-phase, while warning that reactance, power factor, harmonics, large feeders, and inductive loads need fuller analysis.
- NIST Handbook 100, Copper Wire Tables, checked 4 Sep 2026. It gives standard annealed-copper resistivity as 0.017241 Ω·mm²/m at 20°C and the 0.00393/°C temperature coefficient used here.
- NIST Handbook 109, Aluminum Wire Tables, checked 4 Sep 2026. It gives the conductor-grade aluminium resistivity and temperature relationship used by the estimate.
- Seattle Public Utilities, Electrical Design Calculations, February 2024, checked 4 Sep 2026. Its full AC approximation includes resistance, reactance, and load power factor. Those extra terms are outside this simple resistance-only calculator.
4 mm², 25 m, 20 A, 70°C र 3% सबै उदाहरण मात्र हुन्। यो model ले conductor को DC resistance अनुमान गर्छ। AC reactance, power factor, harmonics, motor starting, unbalanced phase, joints र manufacturer tolerance समावेश छैन।The 4 mm², 25 m, 20 A, 70°C, and 3% values are examples only. This model estimates conductor DC resistance. It excludes AC reactance, power factor, harmonics, motor starting, phase imbalance, joints, and manufacturer tolerance.