कोठालाई कति क्षमताको AC चाहिन्छ, चलाउँदा कति खर्च हुन्छ?What size AC might your room need, and what will it cost to run?

कोठाको नापबाट सुरुको reference हेर्नुहोस्। अनि रोजेको AC र आफ्नो प्रयोगबाट बिजुली खर्च निकाल्नुहोस्। यो नेपालका सबै कोठालाई मिल्ने sizing rule होइन।Check a starting room-size reference, then calculate energy cost for the AC you choose. This is not a sizing rule for every room in Nepal.

01 कोठाको referenceRoom reference
एकाइ बदल्दा नाप पनि बदलिन्छ।Changing units converts your dimensions.

यो ENERGY STAR को room-AC chart हो। 100–2,500 ft² र करिब 8 ft उचाइका लागि मात्र। नेपालको गर्मी, चिस्यान, छाना, झ्याल र insulation को heat-load design यसले गर्दैन।This ENERGY STAR room-AC chart covers 100–2,500 ft² and an approximately 8 ft ceiling only. It does not design for Nepal's heat, humidity, roof, windows, or insulation.

02 रोजेको AC को खर्चCost of your chosen AC
SEER, SEER2, ISEER वा CEER यहाँ नराख्नुहोस्। EER नाम एउटै भए पनि एकाइ फरक हुन सक्छ।Do not enter SEER, SEER2, ISEER, or CEER here. The name EER alone does not identify its units.

70% एउटा नमुना मात्र हो, inverter AC ले यति नै बचाउँछ भन्ने दाबी होइन। Cooling capacity बिजुली input होइन। Nameplate र उही test point को efficiency लिनुहोस्।The 70% value is illustrative, not an inverter-AC saving claim. Cooling capacity is not electrical input. Use capacity and efficiency from the same nameplate test point.

थप unit मा लाग्ने हालको दर राख्नुहोस्। Slab काट्ने भए Mero Ghar बाट पूरा bill जाँच्नुहोस्।Enter the current energy rate for added units. If use crosses tariff slabs, check the whole bill in Mero Ghar.

दुई छुट्टाछुट्टै हिसाबTwo separate calculations

Cooling reference, final sizing होइनCooling reference, not final sizing10,200–12,200 Btu/h0.85–1.02 ton

घाम थाहा नभए छायाँदेखि धेरै घामसम्मको scenario हो। यो वास्तविक load को minimum र maximum होइन।Unknown sun shows shaded-to-sunny scenarios, not a minimum/maximum bound on actual cooling load.

कोठाको क्षेत्रफलRoom area
400 ft² / 37.16 m²
छानेको AC को coolingChosen AC cooling
3.517 kW
Rated electrical inputRated electrical input
1,005 W
औसत electrical inputAverage electrical input
703 W
दिनको ऊर्जाDaily energy
5.63 kWh
यो महिनाको ऊर्जाThis month's energy
168.8 kWh
राखिएको दरमा energy खर्चEnergy cost at your entered rateRs 1,6888 h/day × 30 days
किन्ने वा जडान गर्ने सिफारिस होइनHonesty note: not purchase or installation advice

तराईको गर्मी र चिस्यान, माथिल्लो छाना, ठूलो झ्याल, insulation, खुला ढोका, altitude र thermostat ले load र input बदल्छन्। Chart नेपालमा प्रमाणित heat-load model होइन। HVAC प्राविधिकबाट site load र उपयुक्त AC जाँच गराउनुहोस्। खर्चमा fixed bill charge, maintenance र standby ऊर्जा छैन।Terai heat and humidity, an exposed roof, large windows, insulation, open doors, altitude, and thermostat settings change load and input. The chart is not a Nepal-validated heat-load model. Have an HVAC professional check the site load and suitable equipment. Cost excludes fixed bill charges, maintenance, and energy outside the entered hours.

सूत्र र chart को सीमाFormulas and chart limits

  1. floor area = room length × width; ft² = m² ÷ 0.09290304
  2. reference Btu/h = chart capacity × sun factor + extra occupants × 600 + kitchen allowance
  3. sun factor: shaded 0.9; normal 1; sunny 1.1; unknown spans 0.9–1.1
  4. extra occupants = max(0, people − 2); kitchen allowance = 4,000 Btu/h if applicable
  5. cooling kW = chosen Btu/h × 0.2930711 ÷ 1,000; 1 refrigeration ton = 12,000 Btu/h
  6. rated input W = cooling W ÷ efficiency (W/W), or Btu/h ÷ EER (Btu/Wh)
  7. average input W = rated input W × entered average-input % ÷ 100
  8. measured mode: average input W = measured kWh × 1,000 ÷ measurement hours
  9. period kWh = average input W ÷ 1,000 × hours/day × days; cost = period kWh × entered Rs/kWh

घामको factor chart मा मात्र लाग्छ। Cost को % औसत electrical input को अनुमान हो, cooling load वा efficiency मा अर्को factor होइन। मापन भएको input भए % फेरि लाग्दैन।The sun factor applies only to the chart. The cost percentage is an assumed average electrical input, not a second efficiency or cooling-load correction. Measured input is not multiplied by that percentage.

पूरा ENERGY STAR reference chartFull ENERGY STAR reference chart
8 ft उचाइ, घाम र मानिसको adjustment अघि8 ft ceiling, before sun and occupant adjustments
Area (ft²)Cooling (Btu/h)
100 ≤ area < 1505,000
150 ≤ area < 2506,000
250 ≤ area < 3007,000
300 ≤ area < 3508,000
350 ≤ area < 4009,000
400 ≤ area < 45010,000
450 ≤ area < 55012,000
550 ≤ area < 70014,000
700 ≤ area < 1,00018,000
1,000 ≤ area < 1,20021,000
1,200 ≤ area < 1,40023,000
1,400 ≤ area < 1,50024,000
1,500 ≤ area < 2,00030,000
2,000 ≤ area ≤ 2,50034,000

ठ्याक्कै band को सीमामा ठूलो band लिइन्छ। 2,500 ft² अन्तिम सीमा हो। Chart बाहिर वा उचाइ नमिले sizing देखाइँदैन। ठूलो AC हुँदैमा राम्रो हुँदैन। धेरै ठूलो भए चिस्यान हट्नुअघि नै कोठा चिसो हुन सक्छ।At a shared band boundary, the larger band is used. The final 2,500 ft² limit is included. No sizing is extrapolated outside the chart or for another ceiling height. Bigger is not always better: an oversized AC can cool the room before removing enough humidity.

दुई नमुना हिसाबTwo worked examples

यी बजार specification वा सही AC छानिएको दाबी होइनन्। नाप, efficiency, प्रयोग र दर सबै नमुना हुन्।These are illustrative inputs, not market specifications or claims that the AC is correctly sized.

400 ft², चार मानिस, घाम थाहा छैन400 ft², four people, unknown sun

20 × 20 ft, करिब 8 ft उचाइ, भान्सा होइन। Base 10,000 Btu/h।20 × 20 ft, about 8 ft ceiling, not a kitchen. Base is 10,000 Btu/h.

10,000 × (0.9–1.1) + 2 × 600 = 10,200–12,200 Btu/h

खर्चको छुट्टै नमुना: 12,000 Btu/h AC, 3.5 W/W, औसत 70%, 8 h/day, 30 दिन र Rs 10/kWh।Separate cost scenario: 12,000 Btu/h AC, 3.5 W/W, 70% average input, 8 h/day, 30 days, Rs 10/kWh.

12,000 × 0.2930711 ÷ 3.5 = 1,004.8152 W1.0048152 × 0.7 × 8 × 30 = 168.809 kWh168.8089536 × Rs 10 = Rs 1,688.09

300 ft² को घाम पर्ने भान्सा, तीन मानिस300 ft² sunny kitchen, three people

15 × 20 ft, करिब 8 ft उचाइ। Base 8,000 Btu/h।15 × 20 ft, about 8 ft ceiling. Base is 8,000 Btu/h.

8,000 × 1.1 + 600 + 4,000 = 13,400 Btu/h

खर्चको छुट्टै नमुना: 9,000 Btu/h AC र 12 Btu/Wh EER। यो chart reference भन्दा सानो छ, यसलाई पर्याप्त AC भनेको होइन।Separate cost scenario: 9,000 Btu/h AC and EER 12 Btu/Wh. It is below the chart reference, not a claim of adequate cooling.

9,000 ÷ 12 = 750 W rated input0.750 × 0.5 × 6 h/day × 20 days = 45 kWh45 × Rs 12/kWh = Rs 540

स्रोत र मान्यताSources and assumptions

Unknown sun को range chart का दुई scenario मात्र हो, statistical confidence interval होइन। घरको cooling load वा compressor cycle मौसमबाट निकालिएको छैन। लामो समयको मापन छ भने measured mode लिनुहोस्।The unknown-sun range compares two chart scenarios, not a statistical confidence interval. No cooling load or compressor cycle is predicted from local weather. Prefer measured mode when representative energy measurements are available.